9.4 Faults
The table below show the faults which are directly related to the heat flow function. For the full list of
faults including errors, lockouts, alarms, warnings, setting conflicts and forced commission reasons,
please see section 4 in the Mk8 MM Installation and Commissioning Guide.
Fault Message Description Type
440 Temperature Sensor T1Fault Fault or no comms with T1 sensor Warning
Check wiring and screen on terminals –and T1
441 Temperature Sensor T2 Fault Fault or no comms with T2 sensor Warning
Check wiring and screen on terminals – and T2
442 Temperature Sensor T3 Fault Fault or no comms with T3 sensor Warning
Check wiring and screen on terminals – and T3
443 Make Up Flow Meter Fault Fault or no comms with make up flow
meter
Warning
Check wiring and screen on terminals F- and MF
444 Condensate Flow Meter Fault Fault or no comms with condensate
flow meter
Warning
Check wiring and screen on terminals F- and CF