3 Water Level Control
Page 58 Mk8 MM Expansion Features Installation and Set-Up Guide 04.09.2016
3.8.5 Setting 1
st
Low Level
Figure 3.8.5.i Commission 1
st
Low Level
After storing or updating the 2
nd
low level, press to increase the water level to the 1
st
low
level.
Once the water has risen to the required 1
st
low level, turn the pump off and close the valve. Let the
readings settle and press . If required, the 1
st
low level can be updated by then adjusting
the water level and pressing once the position has been stored.