3P- 0V supply to TDS probe
3T+, 3T- Digital communication connections from TDS probe
1P+ +9V supply to capacitance probe 1
1P- 0V supply to capacitance probe 1
1T+, 1T- Digital communications connections from capacitance probe 1
2P+ +9V supply to capacitance probe 2
2P- 0V supply to capacitance probe 2
2T+, 2T- Digital communications connections from capacitance probe 2
FO1 First Out annunciation line voltage input 1
FO2 First Out annunciation line voltage input 2
FO3 First Out annunciation line voltage input 3
FO4 First Out annunciation line voltage input 4
FO5 First Out annunciation line voltage input 5
FO6 First Out annunciation line voltage input 6
FO7 First Out annunciation line voltage input 7
FO8 First Out annunciation line voltage input 8
FO9 First Out annunciation line voltage input 9
FO10 First Out annunciation line voltage input 10
FO11 First Out annunciation line voltage input 11
FO12 First Out annunciation line voltage input 12
PF Power feed 2A output (230V/110)
FO13 First Out annunciation line voltage input 13
FO14 First Out annunciation line voltage input 14
FO15 First Out annunciation line voltage input 15
HAI External high water auxiliary input
1AI External 1
st
low water auxiliary input
2AI External 2
nd
low water auxiliary input
M/R System alarm mute/reset
TST System test alarm inputs/ shunt switch