Flame Safeguard (MM80001/FSG) Manual
BC: Fuel Pressure Sensor Mode – Fuel 1
Gas: For setting 1, valve proving and pressure limits are checked by an
Autoflame gas sensor. For setting 2, low pressure limit can be checked by
external pressure switch. For setting 3, the system will wait for a mains
voltage input on terminal 55 to confirm that the VPS test is completed. If a
voltage is not detected on terminal 55 within 10 minutes, a lockout will occur.
Please see Autoflame Sensors Guide for options/parameters and wiring
guides on VPS and pressure limits setups.
Oil: For setting 2, pressure limits are checked by an Autoflame oil sensor.
Pressure limits, valve proving
BC: Fuel Pressure Sensor Mode – Fuel 2
Gas: For setting 1, valve proving and pressure limits are checked by an
Autoflame gas sensor. For setting 2, low pressure limit can be checked by
external pressure switch. For setting 3, the system will wait for a mains
voltage input on terminal 55 to confirm that the VPS test is completed. If a
voltage is not detected on terminal 55 within 10 minutes, a lockout will occur.
Please see Autoflame Sensors Guide for options/parameters and wiring
guides on VPS and pressure limits setups.
Oil: For setting 2, pressure limits are checked by an Autoflame oil sensor.
Pressure limits, valve proving
BC: Fuel Pressure Sensor Mode – Fuel 3
Gas: For setting 1, valve proving and pressure limits are checked by an
Autoflame gas sensor. For setting 2, low pressure limit can be checked by
external pressure switch. For setting 3, the system will wait for a mains
voltage input on terminal 55 to confirm that the VPS test is completed. If a
voltage is not detected on terminal 55 within 10 minutes, a lockout will occur.
Please see Autoflame Sensors Guide for options/parameters and wiring
guides on VPS and pressure limits setups.
Oil: For setting 2, pressure limits are checked by an Autoflame oil sensor.
Pressure limits, valve proving
BC: Fuel Pressure Sensor Mode – Fuel 4
Gas: For setting 1, valve proving and pressure limits are checked by an
Autoflame gas sensor. For setting 2, low pressure limit can be checked by
external pressure switch. For setting 3, the system will wait for a mains
voltage input on terminal 55 to confirm that the VPS test is completed. If a
voltage is not detected on terminal 55 within 10 minutes, a lockout will occur.
Please see Autoflame Sensors Guide for options/parameters and wiring
guides on VPS and pressure limits setups.
Oil: For setting 2, pressure limits are checked by an Autoflame oil sensor.
Pressure limits, valve proving