Chapter 3: Configuration and Parameters
Page 3–75Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
parameTer deTails – “log” menu of parameTers (ConTinued)
Each SR55 is tested at the factory, and each unit may have a brief log history from this
testing.
log “overload log” parameTers
P21.0 – Last overload Type:
Description:
Read Only
Displays the overload level at the end of the last successful start.
Range: Modbus Decimal Value: Default:
0% to 100% linear scale ( 1 = 0.006104 % ) 0%
Modbus Address: Modbus Format:
40320 ( 9D80 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Log → Overload Log → Last Overload
P21.1 – Last overload -1 Type:
Description:
Read Only
Displays the overload level at the end of the last successful start -1.
Range: Modbus Decimal Value: Default:
0% to 100% linear scale ( 1 = 0.006104 % ) 0%
Modbus Address: Modbus Format:
40321 ( 9D81 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Log → Overload Log → Last Overload -1
P21.2 – Last overload -2 Type:
Description:
Read Only
Displays the overload level at the end of the last successful start -2.
Range: Modbus Decimal Value: Default:
0% to 100% linear scale ( 1 = 0.006104 % ) 0%
Modbus Address: Modbus Format:
40322 ( 9D82 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Log → Overload Log → Last Overload -2
P21.3 – Last overload -3 Type:
Description:
Read Only
Displays the overload level at the end of the last successful start -3.
Range: Modbus Decimal Value: Default:
0% to 100% linear scale ( 1 = 0.006104 % ) 0%
Modbus Address: Modbus Format:
40323 ( 9D83 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Log → Overload Log → Last Overload -3
P21.4 – Last overload -4 Type:
Description:
Read Only
Displays the overload level at the end of the last successful start -4.
Range: Modbus Decimal Value: Default:
0% to 100% linear scale ( 1 = 0.006104 % ) 0%
Modbus Address: Modbus Format:
40324 ( 9D84 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Log → Overload Log → Last Overload -4