Page 3–76 Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 3: Configuration and Parameters
parameTer deTails – “log” menu of parameTers (ConTinued)
Each SR55 is tested at the factory, and each unit may have a brief log history from this
testing.
P21.5 – Last overload -5 Type:
Description:
Read Only
Displays the overload level at the end of the last successful start -5.
Range: Modbus Decimal Value: Default:
0% to 100% linear scale ( 1 = 0.006104 % ) 0%
Modbus Address: Modbus Format:
40325 ( 9D85 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Log → Overload Log → Last Overload -5
P21.6 – Last overload -6 Type:
Description:
Read Only
Displays the overload level at the end of the last successful start -6.
Range: Modbus Decimal Value: Default:
0% to 100% linear scale ( 1 = 0.006104 % ) 0%
Modbus Address: Modbus Format:
40326 ( 9D86 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Log → Overload Log → Last Overload -6
P21.7 – Last overload -7 Type:
Description:
Read Only
Displays the overload level at the end of the last successful start -7.
Range: Modbus Decimal Value: Default:
0% to 100% linear scale ( 1 = 0.006104 % ) 0%
Modbus Address: Modbus Format:
40327 ( 9D87 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Log → Overload Log → Last Overload -7
P21.8 – Last overload -8 Type:
Description:
Read Only
Displays the overload level at the end of the last successful start -8.
Range: Modbus Decimal Value: Default:
0% to 100% linear scale ( 1 = 0.006104 % ) 0%
Modbus Address: Modbus Format:
40328 ( 9D88 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Log → Overload Log → Last Overload -8
P21.9 – Last overload -9 Type:
Description:
Read Only
Displays the overload level at the end of the last successful start -9.
Range: Modbus Decimal Value: Default:
0% to 100% linear scale ( 1 = 0.006104 % ) 0%
Modbus Address: Modbus Format:
40329 ( 9D89 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Log → Overload Log → Last Overload -9

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct Stellar SR55 Series and is the answer not in the manual?

Automation Direct Stellar SR55 Series Specifications

General IconGeneral
BrandAutomation Direct
ModelStellar SR55 Series
CategoryController
LanguageEnglish

Related product manuals