Chapter 3: Configuration and Parameters
Page 3–81Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
parameTer deTails – “deviCe” menu of parameTers (ConTinued)
P26.4 – Anybus / ModbusTCP / EtherNetIP Type:
Description:
Read Only
Modbus TCP Communication Module.
Active only with Anybus / ModbusTCP / EtherNetIP Communication Module installed.
Range: Modbus Decimal Value: Default:
• Address
• Serial Number
• Firmware Version
• Connection
– –
Modbus Address: Modbus Format:
– –
Touchscreen Menu Path:
Home → Device → Networks → Anybus / Modbus TCP / EtherNet/IP
P26.5 – Timeout mS Type:
Description:
Read/Write
Communications trip Timeout period. To prevent a ‘Communications Trip’ (If enabled), a
parameter must be written to or read within this time period.
Range: Modbus Decimal Value: Default:
0ms – 60,000ms linear scale ( 1 = 1 ms ) 5000ms
Modbus Address: Modbus Format:
15808 ( 3DC0 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Device → Networks → Timeout mS
P26.6 – Communications Shutdown Hold. Reg. Type:
Description:
Read/Write
This works in conjunction with the ‘Communications Trip.’
Range: Modbus Decimal Value: Default (decimal):
• Off : If the ‘Communication Trip’ is turned ‘On’ the unit will trip
if the communications fail.
• On : If the ‘Communication Trip’ is turned ‘On’ the unit will shut
down instead of tripping if the communications fail.
• 0
• 1 • ON (1)
Modbus Address: Modbus Format:
53802 ( D22A hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Device → Networks → Communications Shutdown