Page 3–82 Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 3: Configuration and Parameters
parameTer deTails – “deviCe” menu of parameTers (ConTinued)
deviCe parameTers
P27.0 – Reset Defaults Hold. Reg. Type:
Description:
Read/Write
Restores the SR55 to the factory defaults.
Reset to factory defaults does not reset configurations that were set up in the Anybus modules,
because the configuration is stored in the communication module; not the starter.
Range: Modbus Decimal Value: Default (decimal):
No
Yes
0
1
No (0)
Modbus Address: Modbus Format:
62080 ( F280 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Device → Reset Defaults
warning: if a passcode is seT in The sr55 and losT/forgoTTen, you musT conTacT Technical
supporT for assisTance (800) 633-0405. The procedure will require The uniT be facTory reseT by
an auThorized represenTaTive. reseT defaulTs parameTer will noT be available if screen lock is
enabled.
P27.1 – About Type:
Description:
Read Only
Gives the SR55 model number, serial number, and current firmware versions.
Range: Modbus Decimal Value: Default:
Model number
Serial Number
Firmware versions
Modbus Address: Modbus Format:
Touchscreen Menu Path:
Home → Device → About
P27.2 – Screen Lock Hold. Reg. Type:
Description:
Read/Write
Stops unauthorized access to read/write parameters.
Range: Modbus Decimal Value: Default (decimal):
Off
On
0
1
Off (0)
Modbus Address: Modbus Format:
12992 ( 32C0 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Device → Screen Lock
warning: ensure The passcode is known before seTTing This parameTer. if a passcode is seT in The
sr55 and losT/forgoTTen, you musT conTacT Technical supporT for assisTance (800) 633-0405. The
procedure will require The uniT be facTory reseT by an auThorized represenTaTive.
P27.3 – Date Format Hold. Reg. Type:
Description:
Read/Write
Allows the date format to be changed to American.
Range: Modbus Decimal Value: Default:
dd/mm/yyyy
mm/dd/yyyy
0
1
dd/mm/yyyy
Modbus Address: Modbus Format:
13248 ( 33C0 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Device → Date Format

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct Stellar SR55 Series and is the answer not in the manual?

Automation Direct Stellar SR55 Series Specifications

General IconGeneral
BrandAutomation Direct
ModelStellar SR55 Series
CategoryController
LanguageEnglish

Related product manuals