Page 3–50 Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 3: Configuration and Parameters
parameTer deTails – “i/o” menu of parameTers (ConTinued)
i/o “analog inpuT” parameTers
P12.0 – Analog Input Type Hold. Reg. Type:
Description:
Read/Write
Defines the function of the Analog Input (AI).
Range: Modbus Decimal Value: Default (decimal):
0–10V : The input voltage varies from 0 to 10V.
4–20mA : The input varies from 4 to 20mA.
0
1
0–10V (0)
Modbus Address: Modbus Format:
Touchscreen Menu Path:
P12.1 – Analog Input: Select Function Hold. Reg. Type:
Description:
Read/Write
Allows the Analog Input to be mapped to different functions. The selected function will change in
proportion with the input.
Range: Modbus Decimal Value: Default (decimal):
Off
Current Limit Start
Current Shearpin
Current Overload
0
420
431
441
Off (0)
Modbus Address: Modbus Format:
9664 ( 25C0 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → I/O → Analog Inputs → Select Function (Analog Input)
Examples of P12.1 Analog Input Fuction Selections
AI Function
Settings:
Modbus
Dec. Value:
Example:
Current
Limit Start
420
AI signal controls P3.3 Start Current Limit Level. Ex: Water pumping
system with high head; nearly vertical lift. AI signal keeps P3.3 low
at start to slowly rotate motor to control flow until height is reached,
then AI signal increases P3.3 to allow motor to accelerate to full speed.
Usually PLC control.
Current
Shearpin
431
AI signal controls P5.6 Shearpin Trip Current. Ex: Applications such
as opening and closing sluice gates or doors, which require different
running current limits for opening vs. closing. AI signal changes P5.6
as needed, usually via PLC control. P5.5 Shearpin Trip is turned OFF
when P5.6 level is reached; however an output should be used to stop
the motor via a relay in the motor stop circuit.
Current
Overload
441
AI signal controls P5.9 Overload Level. Ex: Motor testing. AI signal
changes P5.8 as needed to test different motors.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct Stellar SR55 Series and is the answer not in the manual?

Automation Direct Stellar SR55 Series Specifications

General IconGeneral
BrandAutomation Direct
ModelStellar SR55 Series
CategoryController
LanguageEnglish

Related product manuals