Chapter 3: Configuration and Parameters
Page 3–69Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
parameTer deTails – “log” menu of parameTers (ConTinued)
Each SR55 is tested at the factory, and each unit may have a brief log history from this
testing.
P19.2 – Last Peak Stop Current -2 Type:
Description:
Read Only
Displays the peak current of the last successful stop -2.
Range: Modbus Decimal Value: Default:
Peak Current: 0A – 10,000A
Peak Current Time: hh:mm:ss
linear scale (1 = 1mA)
Current (A) = (Value / 1000)
Time (ms) since midnight
(bytes5,4,3,2) and Days since
01/01/1984 (bytes1,0)
0A
GMT
Modbus Address: Modbus Format:
Peak Current: 39044/39045 ( 9884/9885 hex )
Peak Current Time: 39110/39111/39112 ( 98C6/98C7/98C8 hex )
32-bit unsigned
6 Bytes
Touchscreen Menu Path:
Home → Log → Stop Current Log → Last Peak Stop Current -2
P19.3 – Last Peak Stop Current -3 Type:
Description:
Read Only
Displays the peak current of the last successful stop -3.
Range: Modbus Decimal Value: Default:
Peak Current: 0A – 10,000A
Peak Current Time: hh:mm:ss
linear scale (1 = 1mA)
Current (A) = (Value / 1000)
Time (ms) since midnight
(bytes5,4,3,2) and Days since
01/01/1984 (bytes1,0)
0A
GMT
Modbus Address: Modbus Format:
Peak Current: 39046/39047 ( 9886/9887 hex )
Peak Current Time: 39113/39114/39115 ( 98C9/98CA/98CB hex )
32-bit unsigned
6 Bytes
Touchscreen Menu Path:
Home → Log → Stop Current Log → Last Peak Stop Current -3
P19.4 – Last Peak Stop Current -4 Type:
Description:
Read Only
Displays the peak current of the last successful stop -4.
Range: Modbus Decimal Value: Default:
Peak Current: 0A – 10,000A
Peak Current Time: hh:mm:ss
linear scale (1 = 1mA)
Current (A) = (Value / 1000)
Time (ms) since midnight
(bytes5,4,3,2) and Days since
01/01/1984 (bytes1,0)
0A
GMT
Modbus Address: Modbus Format:
Peak Current: 39048/39049 ( 9888/9889 hex )
Peak Current Time: 39116/39117/39118 ( 98CC/98CD/98CE hex )
32-bit unsigned
6 Bytes
Touchscreen Menu Path:
Home → Log → Stop Current Log → Last Peak Stop Current -4