123
Scenario Delay
This function cause a time delay in the scenario execution. The maximum time to declare a delay in a scenario execution is 600
seconds. In order to execute the scenario with a delay, activate the scenario delay function and then activate scenario execution
via the General function. The period of the delay from the moment of activation of a scenario is signalled by a purple LED blinking.
Select audio source
This function enables easy execution of the dynamic matricing function. Dynamic matricing consists of creating a matrix
( combining a source to speaker lines) from a zone microphone or GUI in any conguration according to the user’s current needs.
Thefollowing items can be assigned as an audio source: messages, reman microphones and all available zone microphones and
their audio inputs. In order to initiate dynamic matricing, select dedicated Zone selection buttons in the given order: highlight
the zone or zone group to which we want to transmit to, then – using the Source selection button – initiate transmission of the
programmed source into the selected zones.
Select Zone
The zone selection function serves to assign one zone or a zone group to a selected button. Having selected the function in the
congurator, assign the selected zone in the Select Zone eld, and then select one of the activation modes.
Silence
This is a global function which deletes all active sound sources of the BGM or General priorities. This function is available only for
logical inputs and the ABT-DFMS reman microphone buttons and may be activated even if the reman microphone is not in
the alarm mode. If the Silence mode is active (a red LED on the microphone at the Silence function button is on), then BGM and
General matrices cannot be activated. Deactivation of the function unblocks priority matricing.
Skip Scenarios Delay
This is a global function and results in prompt execution of all scenarios for which the delay time countdown has started
(purple LED blinking).
Stop Scenario
The function results in stopping execution of a scenario, as declared in the congurator. The scenario stop causes switching o
all active matrices included in the scenario, whereas the status of the relay outputs which might have been a part of the scenario
remains consistent with the programmed state at the moment of stopping the scenario.
Start / stop matricing
The function enables activation or deactivation, via one logical input or button on the zone / reman microphone, of one or many
matrices, as dened in the congurator. Each matrix can be assigned an individual activation mode – start / stop / toggle.
Zone(s) o
The function acts on the principle of dynamic assignment, i.e. in order to activate the function, one needs to follow a prede-
ned order. The rst activity is to select a zone or many zones using the programmed button Select Zone, then the Zone(s)
o button is selected. Thus activated, the function causes irreversible disconnection of all active sound sources of BGM,
General, Service priorities.
External Fault CIN
The External fault CIN can only be assigned to a system logical input. Having activated the logical input to which the function is
assigned, in the fault window on the GUI, as well as in system logs, an entry will be displayed with the name of the logical input.
Change the name of the logical output in order to identify the fault-reporting device in an unequivocal way.