131
The time is determined in minutes / The time interval [15 ... 300 minutes]
Default state – checkbox enclosed, active function
Default activation time: 60 minutes
AutoStandby function is available in the Basic Conguration:
Each attempt of audio broadcasting while Standby is active causes:
»
exit from Standby to the Normal mode (when operating on the primary power source), regardless on the priority of a message ;
»
exit from Standby mode to the BattMode (when there is lack of primary power supply) only when messages will have
Service / Emergency priority.
The maximum duration of the activation process of exit from Standby mode to broadcasting message is shorter than 500 ms.
Because the function has been implemented in Phase 1 of AutroVoice miniVES development and its activation is dynamic
(Zoneselection then pressing Power Save button) there is need to change the way of its implementation from the dynamic to
static (PAzones strictly dened in the congurator are to be deactivated / activated by friendly Power Save features.
Diagram of transition Normal mode – Battery mode – Standby mode is shown below:
Normal
(230 V Powered)
BattMode
(Battery Powered)
Standby
(230 V or
Battery Powered)
Condition:
Restored Power 230 VAC
TODO:
Deactivate PowerSave
(Restore Saved Audio Matrix)
Condition:
Lost Power 230 VAC
TODO:
Activate PowerSave
(Save and Mute Active
Audio Matrix General, BGM)
Condition:
No Active Audio Matrix (Emergency/Service)
No Alarm Mode
Trigger:
Activate PowerSave
(by Timer, Logical Input, Key, Auto Power-Save)
TODO:
Save and Mute Active Audio Matrix: General, BGM
Condition:
No Alarm Mode
No Active Emergency/Service Audio Matrix
Condition:
230 VAC Present
Trigger:
Created Audio Matrix (Emergency/Service/General/BGM)
Power Save O (Timer, Logical Input, Key)
TODO:
Restore Saved Audio Matrix
Condition:
230 VAC
Trigger:
Created Audio Matrix (Emergency/Service)