132
COMPACT VOICE ALARM SYSTEM
SERVICE MANUAL
2. The list of faults reported by the system
E: Error – fault description visible on GUI of the control unit
W: Warning – access to this type of the information via Selector software – System Report only
I: Info – access to this type of the information via Selector software – System Report only
“E0002” – “Function backplane power failure” – no 12V in the functional part
“E0001” – “Function backplane power failure” – no 5V in the functional part
“E0003” – “Function backplane power failure” – no -12V in the functional part
“E0011” – “Control backplane power failure” – no 5V control part
“E0012” – “Control backplane power failure” – no 12V control part
“E0013” – “Control backplane power failure” – no -12V control part
“E0023” – “Power control system failure” – damage control system functional part
“E0022” – “Power control system failure” – damage control system control part
“E0101” – “Device do not respond”
“E0102” – “Logical input open”
“E0103” – “Logical input short”
“E0104” – “Speaker line ground fault”
“E0105” – “Speaker line short”
“E0106” – “Files integrity error”
“E0107” – “Speaker line impedance error”
“E0108” – “Speaker line open”
“E0109” – “EOL error”
“E0110” – “Interruption of the audio path”
“E0111” – “Battery failure”
“E0112” – “Backup power / PSM missing”
“E0113” – “230V AC power failure”
“E0114” – “Amplier overheat”
“E0115” - “Fuse failure”
“E0116” - “Power system manager failure”
“E0117” - “48V DC error”
“E0118” – “No communication with ABT-ISLE”
“E0119” – “Loop link error”
“E0200” – “ABT-DFMS missing”
“E0201” – “Evacuation button error”
“E0202” – “Backup audio path interruption”
“E0203” – “CPLD verication error”
“E0204” – “Interruption of the audio path in ABT-DFMS capsule”
“E0205” – “Internal hardware error”
“E0206” – “Error triggered from logical input”
“E0207” – “Integrity state error”
“E0208” – “Test generator failure”
“E0209” – “No conditions for measurement”
“W0001” – “Function backplane power overload” – over current power supply 5V functional part
“W0002” – “Function backplane power overload” – over current power supply 12V functional part
“W0003” – “Function backplane power overload” – over current power supply -12V functional part
“W0011” – “Control backplane power overload” – over current power supply 5V control part
“W0012” – “Control backplane power overload” – over current power supply 12V control part
“W0013” – “Control backplane power overload” – over current power supply -12V control part
“W0021” – “Power supply overheat” – power supply overheat functional part
“W0022” – “Power supply overheat” – power supply overheat control part
“W0031” – “System operates on battery power”
“W0101” – “Standby mode activation”
“W0102” – “Standby mode deactivation”
“W0103” – “Device Initialization error, dev=%x”
“I0101” – “Alarm mode activation”
“I0102” – “Alarm mode deactivation”
“I0103” – “Event activation %xx”