Service Commands
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 105
Step Actions to be taken Display Indication
To select DETECTION ZONE TEST, press 1.
To select LEAVE TEST MODE, press 2.
(Only Detection Zones in Test Mode will appear
in the display).
Use the keyboard to enter text into the input box
-
OR ,- as shown in this example:
To select a Zone Name, press
then scroll downwards or upwards by pressing
To leave Test Mode for the selected zone (in this
example CANTEEN is chosen), press twice on
SERVICE
DZ TEST
1 ENTER TEST MODE
2 LEAVE TEST MODE
19:23
SERVICE
DZ TEST
1 ENTER TEST MODE
2 LEAVE TEST MODE
19:23
SERVICE
19:23
LEAVE TEST MODE DZ
Zone Name:
CANTEEN
KITCHEN
OFFICES
WORKSHOP
SERVICE
19:23
LEAVE TEST MODE DZ
Zone Name:
CANTEEN
KITCHEN
OFFICES
WORKSHOP
SERVICE
19:23
LEAVE TEST MODE DZ
Zone Name:
CANTEEN
KITCHEN
OFFICES
WORKSHOP
SERVICE
19:23
LEAVE TEST MODE DZ
Zone Name:
CANTEEN
KITCHEN
OFFICES
WORKSHOP
SERVICE
DZ TEST
1 ENTER TEST MODE
2 LEAVE TEST MODE
19:23
SERVICE
DZ TEST
1 ENTER TEST MODE
2 LEAVE TEST MODE
19:23
To ensure that all selected detection zones leave Test Mode after carrying out this
procedure, press the reset button on the front panel.