Service Commands
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 104
Step Actions to be taken Display Indication
7
To enter Test Mode for the selected zone (in this
example CANTEEN is chosen), press twice on
14.3.1.3 Leaving Test Mode
The procedure below describes how to leave test mode for a selected
zone (LEAVE TEST MODE).
Step Actions to be taken Display Indication
1
To enter the Main Menu, press the Menu button
2
To select SERVICE, press 5.
3
To select TEST, press 1.
SERVICE
DZ TEST
1 ENTER TEST MODE
2 LEAVE TEST MODE
19:23
SERVICE
DZ TEST
1 ENTER TEST MODE
2 LEAVE TEST MODE
19:23
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 REPORT
5 UPGRADE
6 REMOTE ACCESS
7 DUAL SAFETY
8 OIL & GAS COMMANDS
SERVICE
TEST
1 DETECTION ZONE TEST (EN 54)
2 OUTPUT TEST
19:23