Programming Page 14/44
MID_M2000_BA_02_1004
Quick Setup
Totalizer Unit
This parameter establishes the units of measure for the totalizers:
Full Scale Flow
This parameter sets the maximum flow the system is expected to
measure. This parameter has influence on other system parameters.
These parameters include: Frequency output and current output.
In terms of flow velocity, the meter’s limit are from 0.1 to 12 m/sec.
Moreover the values for Low Flow Cut-off and limits monitoring depend
on Full Scale Flow.
The full scale flow is valid for both flow directions.
Note: If the flow rate exceeds the full scale setting, an error message
indicates that the configured full scale range has been exceeded.
Low Flow Cut-off
Low Flow Cut-off defines the threshold at which flow measurement will
be forced to zero. The cutoff value can be from 0 % to 9.9 % of the full
scale flow. Increasing the threshold will help prevent false reading
during “no flow” conditions possible caused by vibrations or liquid
fluctuations.
Unit Unit
L Liters UKG Imperial Gallons
HL HectoLiters Lb Pounds
M³ Cubic Meters Oz Fluid Ounces
CFt Cubic Feet Aft Acre Feet
USG U.S. Gallons BBL Barrel
MG MegaGallons