EasyManuals Logo

Banner SC26-2 User Manual

Banner SC26-2
117 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #70 background imageLoading...
Page #70 background image
Input Circuit
Input Signal COS Timing Rules
Stop State—SO turns Off when
3
: Run State—SO turns On when
4
:
2X Complementary A and B
4 Terminals 5 Terminals
PNP
24V
OFFON OFFON
At least 1 channel (A or B) within a pair of
contacts is in the Stop state.
Simultaneous: A and B are concurrently
in the Stop state, then contacts within a
channel in the Run state within 400 ms
(150 ms for two-hand control), both
channels are in the Run state within 3
seconds (0.5 seconds for two-hand
control).
Concurrent: A and B are concurrently in
the Stop state, then contacts within a
channel in the Run state within 3 seconds.
Both channels are in the Run state with no
simultaneity.
4-Wire Safety Mat
2-Ch, 4 Terminals
One of the following conditions is met:
Input channels are shorted
together (normal operation)
At least 1 of the wires is
disconnected
One of the normally low
channels is detected high
One of the normally high
channels is detected low
Each channel detects its own pulses.
Signal Debounce Times
Closed-to-Open Debounce Time (from 6 ms to 1000 ms in 1 ms intervals, except 6 ms to 1500 ms for mute
sensors). The closed-to-open debounce time is the time limit required for the input signal to transition from the high (24
V dc) state to the steady low (0 V dc) state. This time limit may need to be increased in cases where high-magnitude
device vibration, impact shock, or switch noise conditions result in a need for longer signal transition times. If the
debounce time is set too short under these harsh conditions, the system may detect a signal disparity fault and lock out.
The default setting is 6 ms.
CAUTION: Debounce and Response
Any changes in the debounce times may affect the Safety Output response (turn Off) time.
This value is computed and displayed for each Safety Output when a configuration is created.
Open-to-Closed Debounce Time (from 10 ms to 1000 ms in 1 ms intervals, except 10 ms to 1500 ms for mute
sensors). The open-to-closed debounce time is the time limit required for the input signal to transition from the low (0 V
dc) state to the steady high (24 V dc) state. This time limit may need to be increased in cases where high magnitude
device vibration, impact shock, or switch noise conditions result in a need for longer signal transition times. If the
debounce time is set too short under these harsh conditions, the system may detect a signal disparity fault and lock out.
The default setting is 50 ms.
3
Safety Outputs turn Off when one of the controlling inputs is in the Stop state.
4
Safety Outputs turn On only when all of the controlling inputs are in the Run state and after a manual reset is performed (if any safety inputs are
configured for Manual reset and were in their Stop state).
XS/SC26-2 Safety Controller
70

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Banner SC26-2 and is the answer not in the manual?

Banner SC26-2 Specifications

General IconGeneral
BrandBanner
ModelSC26-2
CategoryController
LanguageEnglish

Related product manuals