Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
124
of 208
4.3
P1211
A setting of 100% is equal to the rated output current of the drive.
During acceleration, the b maXX
®
1000 output current may increase abruptly and exceed
the value specified by ZP1212– due to rapid acceleration or excessive load on the motor.
When this function is enabled, the b maXX
®
1000 will stop accelerating and keep the out-
put frequency constant until the current drops below the maximum value.
Figure 54: Over-current stall prevention during acceleration
Value Meaning
0.0 Disabled: over-voltage stall prevention with brake unit or brake resistor
330.0 to 410.0 V
DC
230 V device for 230 V mains voltage
660.0 to 820.0 V
DC
460 V device for 460 V mains voltage
P1211
Überstrom Abschaltschutz während Hochlauf 0 to 250 %
EE Over-current stall prevention level during accel-
eration
170 %
STOP BM_u_OverCurrentStallPreventionLevelAccel 1:1
Value Meaning
0 Disabled
20 to 250 % Enabled