Parameter
Parameter manual b maXX
®
1000
Document no. 5.07004.03
125
of 208
4
P1212
If the output current exceeds the setting specified in ZP1212– when the drive is operat-
ing, the drive will decrease its output frequency to prevent the motor stall. If the output
current is lower than the setting specified in ZP1212–, the drive will accelerate again to
catch up with the set frequency command value.
Figure 55: Over-current stall prevention during operation
P1212
Überstrom Abschaltschutz während Betrieb 0 to 250 %
EE Over-current stall prevention level during oper-
ation
170 %
STOP BM_u_OverCurrentStallPreventionLevelOper 1:1
Value Meaning
0 Disabled
20 to 250 % Enabled