Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
126
of 208
4.3
P1213
This parameter determines the operation mode of the drive after the over-torque (OL2)
error code 0509
hex
is detected via the following method: if the output current exceeds the
over-torque detection level ZP1214 longer than the setting of ZP1215 over-torque de-
tection time, the warning message „OL2“ is displayed. If a multi-functional output terminal
is set to over-torque detection (ZP1110 to ZP1117 = 04), the output is on. Please refer
to ZP1110 to ZP1117 for details.
P1214
This setting is proportional to the rated output current of the drive.
P1215
This parameter sets the time for how long over-torque must be detected before „OL2“ is
displayed.
P1213
Momenten-Überlast Erkennung 0 to 4
EE Over-torque detection mode 0
STOP BM_u_OverTorqueDetectMode 1:1 -
Value Meaning
0 Over-torque detection disabled
1 Over-Torque detection enabled during constant speed operation. After over-torque is
detected, keep running until I²t ZP1216 or OL (overload) occurs.
2 Over-Torque detection enabled during constant speed operation. After over-torque is
detected, stop running.
3 Over-Torque detection enabled during acceleration. After over-torque is detected, keep run-
ning until I²t ZP1216 or OL (overload) occurs.
4 Over-Torque detection enabled during acceleration. After over-torque is detected, stop run-
ning.
P1214
Momenten-Überlast Erkennung Grenze 10 to 200 %
EE Over-torque detection mode level 150
ON BM_u_OverTorqueDetectModeLevel 1:1 -
P1215
Momenten-Überlast Erkennung Zeit 0.1 to 60.0 s
EE Over-torque detection mode time 0.1 s
STOP BM_u_OverTorqueDetectModeTime 10:1 -