P1216
This function is used to protect the motor from overloading or overheating. I²t > 100 %
(OL) error code 0063
hex
.
This parameter sets the time the overtorque must be detected before (OL2) error code
0509
hex
for ZP1213–.
Figure 56: Electronic thermal overload relay
P1216
Elektron. thermische Überlast Relais Auswahl 0 to 2
EE Electronic thermal overload relay selection 2
STOP BM_u_ElectronicThermalOverloadRelaySelection 1:1 -
Value Meaning
0 Operate with standard motor (self-cooled by fan)
1 Operate with a special motor (forced external cooling)
2 Operation disabled