Basic of CAN
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
202
of 208
B.3
m Status word
6041
hex
= P0301 (b maXX
®
1000 parameter)
The status word used in the status machine of the unit control
1)
: These Bits are low-active.
2)
: Display operational status
NAME Index Sub-index Data type Access type Default
value
Status word 6041
hex
00
hex
U16 RO 0
hex
Bit-No. Meaning
0
2)
1: ready to operate
0: not ready to operate
1
2)
1: switched on
0: not ready for use
2
2)
1: operation enabled
0: operation inhibited
3
2)
1: error
0: no error
4
1)2)
1: mains voltage/DC-link voltage is present
0: mains voltage/DC-link voltage is not present
5
1)2)
1: no requirements quickstop
0: quickstop (or quickstop requirement is present)
6
2)
1: inhibit start
0: no inhibit start
7 1: warning
0: no warning
8 RFG stop
9 Reserved
10 1: set value reached
0: set value not reached
11 1: internal limit active (for example: current limit, speed limit…)
0: not internal limit active
12 Speed =0, output frequency = 0
13 Reserved
14 Reserved
15 Status synchronous drive = True