HB-37420-810-01-25F-EN SMX100 Installation manual.docx Page 187 of 260
Version: 25F
5.8 Connection of the external encoder supply
5.8.1 Incremental, HTL, SIN/COS, SSI
1) Only SMX111-2, SMX121-2(/2) and SMX112-2, SMX122-2(A)(/2)
2) Only SMX112, SMX122(A) (/2) and SMX112-2, SMX122-2(A) (/2)
3) Only SMX112-2, SMX122-2(A) (/2)
The SMX100 module supports encoder voltages of 5V, 8V, 10 V, 12V and 24V, which are
internally monitored in accordance with the chosen configuration.
If an encoder system is not supplied through the SMX module, a supply voltage still needs to be
connected to terminal X13 or X15 and configured accordingly.
The encoder supply must be protected with a fuse of max. 2A.
Safety note:
• The GND connection of the encoder must be connected to the GND of the SMX
Monitoring of the supply voltage in accordance with the chosen nominal voltage: