HB-37420-810-01-25F-EN SMX100 Installation manual.docx Page 69 of 260
Version: 25F
3.3 Derating outputs
Maximum current load based on temperature.
This derating should be considered for all 2A outputs (IO-Board and REL-Board)!
2A outputs can be fully loaded at an ambient temperature of up to 30°C.
From a ambient temperature from 30°C to maximum 50°C, the 2A outputs can be loaded to a
maximum of 1.8A. The maximum total current is 10A.
3.4 Identification
The type plate is located on the left side wall of the module and contains the following
information:
3.4.1 Type plate
Type designation
Part number
Serial number
Identification of hardware release
Identification of software release
Safety category
Input characteristics
Output characteristics
Date of manufacture (week/year)
Type plate SMX100 (image enlarged)