Installation manual
HB-37420-810-01-25F-EN SMX100 Installation manual.docx Page 251 of 260
Version: 25F
12.3.7.2 Validation of FUP against AWL and parameters by means of validation
report.
The programming that took place in the FUP must be compared with the AWL-listing of the
validation report.
Example AWL-listing in validation report
Validation report
OLC-program
Name:
<leer>
Index
Command
Operand
validated
1
S1
SLI_EN.1
2
S1
SLI_EN.2
3
S1
SLI_EN.3
4
S1
SCA_EN.1
5
S1
SCA_EN.2
6
S1
SCA_EN.3
7
S1
SLS_EN.2
8
S1
SCA_EN.4
9
S1
SLS_EN.3
10
S1
SLS_EN.4
11
S1
SLI_EN.5
12
SQH
13
LD
E0.1
14
ST
MX.2
15
SQC
16
SQH
17
LD
E0.3
18
AND
E0.4
19
ST
MX.3
20
SQC
Step-by-step testing is recommended. The test all the batter, the more structured the
programming in FUP has been made.
After checking the program one must also check the parameters against the targets set in
the specifications by means of comparison.
Example SLS:
Validation report
Safe Limited Speed (SLS)
Index
Parameters
Value
validated
SLS - 0
Chosen axis:
1
Speed threshold:
2
0
SLS - 1
Chosen axis:
1
Speed threshold:
500
0
SLS - 2
Chosen axis:
1
Speed threshold:
2
0
Acceleration threshold
2
0
SLS - 3
Chosen axis:
1
Speed threshold:
2
0
Assigned SSX-ramp
0