Configuration and testingConfiguration and testing
CC612(4G)_D00325_04_M_XXEN/03.2019
35
6.5 Manufacturer tab
Operator Password
Set a new password to access the operator web
interface.
State page password
protection
Protect the web interface state tab by the configured
password.
Parameter Description
ChargePoint Vendor
Mandatory identifies the vendor of the
ChargePoint.
ChargePoint Model
Mandatory, identifies the model of the
ChargePoint. Please note that the default value
"CC612" is reserved and cannot be used on non-
CC612 models.
Charge controller serial number Charge controller serial number
Meter configuration (OCPP)
The type of meter used for the charging socket
and its connector. This is relevant for OCPP
transactions.
Pulses per kWh (S0 meter) S0 Meter Pulses per kWh
LED type
The type of LED device connected to the charge
controller if any.
Dual LED board mode
The behaviour for dual LED boards. When set to
"ON", the dual LED board shows for left and right
LEDs independent states for Master and Slave.
When set to "OFF", LEDs operate in clone mode:
Left and right LEDs show the same pattern and
color, presenting the state of the main/Master
device.
Type of Display
The type of display connected to the charge
controller if any.
HMI Pattern On Relay 2 (K2)
The behaviour for the relay 2 (K2) to be used for
an external indicator light such as an LED or
blinking light. Use option "On" while vehicle
connected for integration with parking
management system by Scheidt & Bachmann. To
use two contactors in series that are to be
controlled separately, use the function "ON while
charging".
Parameter Description
Enable RFID
Enables or disables the RFID reader. Allows
preventing error messages if no reader is
installed.
Maximum Current (A)
The maximal current of this charge point in
Ampere
Fixed cable attached
Setting this to "On" indicates that the charger has
a fixed cable attached and does NOT need to lock
a cable in a socket. ATTENTION: This is safety
relevant!
Detect Control Pilot Diode
Set this value to "On" if you want to check before
charging if the diode connected to the Control
Pilot line is connected or not.
Door hatch installed
Set to "On" if a hatch is installed in the charge
point. Note that this parameter is relevant only
for CC612.
Redetect actuator
Set this value to "On" if you want to request a
redetection of the connected type 2 socket
locking actuator upon the next boot.
Schuko Socket
Use auxiliary input/output to support additional
Schuko socket.
Power Watchdog
This option monitors whether the power supply
to the charging station or the charging socket is
monitored. The time of interruption is safely
stored and if still possible a message is sent to the
backend.
Authorization Input
Input used for authorization from an external
switch/relay.
Authorization Input Mode
Set if the authorization input can just start or it
can both start and stop a transaction. Note that
Scheidt & Bachmann requires this to be set to Set
this value to "Only start".
Authorization Input Switch Type
Set if the authorization input switch is normally
open or normally closed. Note that Scheidt &
Bachmann requires this to be set to Set this value
to "Normally open".
Temperature threshold 1
Temperature threshold necessary to start
decreasing the current.
Parameter Description