Commissioning flow chart
34
IRDH575_D00089_05_M_XXEN/01.2020
Commissioning of the ISOMETER® function range (2)
Perform a functional test between
system and earth using a suitable
resistance for the mains voltage.
Resistance value: 50% of the
response value ALARM2.