EasyManuals Logo

Bender ISOMETER IRDH575 User Manual

Bender ISOMETER IRDH575
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
Operation and setting
50
IRDH575_D00089_05_M_XXEN/01.2020
6.4 ISO SETUP menu: Setting of the basic ISOMETER®
functions
The response values (Alarm 1/2, prewarning and main alarm), the operating
principle of the alarm relays K1 and K2 (N.O = N/O operation, N.C = N/C ope-
ration), the fault storage behaviour and the selection of the current output
between two different ranges are set in this menu.
6.4.1 Response values Alarm 1 and Alarm 2
The response values Alarm 1 and Alarm 2 are selected with the UP/DOWN
keys and stored with the ENTER key.
6.4.2 Starting the EDS system via the response values ALARM 1
and ALARM 2
The EDS system is started when the value of the insulation resistance falls
below the lowest preset response value, i.e. below both alarm values.
When setting the ISOMETER® response values, make sure that the lower value
of them is within a range which the EDS system is able to find. Therefore it is
recommended to set the ISOMETER® response value according to the respon-
se characteristic curves of the EDS system (Refer to page 102).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender ISOMETER IRDH575 and is the answer not in the manual?

Bender ISOMETER IRDH575 Specifications

General IconGeneral
BrandBender
ModelISOMETER IRDH575
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals