Operation and setting
58
IRDH575_D00089_05_M_XXEN/01.2020
6.6 EDS-SETUP menu: Settings for fault location
This menu allows to carry out the necessary settings for the insulation fault lo-
cation system (EDS).
6.6.1 EDS auto / on / off / pos / 1cycle
A selection of the start and stop conditions for EDS systems and their meaning
are listed below:
 on
The EDS is running continuously, regardless of the insulation value and
the alarm messages from the ISOMETER®. This setting is essential, for
example, for mobile insulation fault location systems such as EDS3060/
3360.
 off
The EDS system is constantly switched off.
 pos470 (EDS47… only)
For continuous measurement at a desired address (EDS4…-12) and a
certain channel. The selected parameters are kept until a new operat-
ing mode is set.
This function is only possible in the Master mode (bus address 1).
The following messages are possible in the POSITION mode.
Note: the messages noCT and short are only generated when the CT
monitoring for the respective channel has been switched on (= factory
setting, menu CT SETUP):
no EDS: no EDS47… of this address available
no Alarm: no insulation fault detected
… mA: indication of the fault current in case of an insula-
tion fault
>1A/>10 A: AC residual current > 1 A (EDS473) or >10 A
(EDS470)
peak fault: measurement disturbed
short: CT input short-circuited
noCT: no CT connected

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender ISOMETER IRDH575 and is the answer not in the manual?

Bender ISOMETER IRDH575 Specifications

General IconGeneral
BrandBender
ModelISOMETER IRDH575
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals