6.7.4 EDS Test
After activating this menu option, the IRDH575 checks all BMS bus nodes dis-
playing the following details:
Device address
Device type
Software version
CT connection
at EDS47… means:
– ok = channel switched on
– off = channel switched off
– noCT = no measuring current transformer connected
– short = measuring current transformer short-circuited
Memory behaviour of the EDS47… (Memory on/off)
Operating principle of the alarm relays of EDS47… (N.O/N.C)
If one of the tested BMS devices does not provide the required properties, no
answer is shown in the list of properties.
Factory setting = off.
6.7.5 EDS Reset
Use this menu option to reset stored fault messages of the connected EDS de-
vices.
Factory setting = off.