8. Factory settings
Menu Submenu Setting
1. EXIT
2. HISTORY INFO
3. ISO SETUP 1. Exit
2. Alarm1: 40 kΩ
3. Alarm2: 10 kΩ
4. K1: N.O Test
5. K2: N.O Test
---------- K3: N.C fixed setting
7. Memory: off
8. M+/M-: 0-20 mA
4. ISO ADVANCED 1. Exit
2. AGH: no
3. Ce. max: 150 µF
4. Measure: AMP
5. Autotest: 24 h
6. Clock: CET (HH:MM)
7. Date:
current date
(DD.MM.YYYY)
8. Test: 12:00
5. EDS.SETUP 1. EXIT
2. EDS: auto
3. System: 3 AC
4. MaxPuls: 25mA
5. K3 Alarm: on

Table of Contents