Operation and setting
62
IRDH575_D00089_05_M_XXEN/01.2020
* = Set the response value of EDS460/490 to < 5 mA
(See EDS460/490 manual, Chap. 6.6.3.2)
** = Set the response value of EDS461/491 to < 0.5 mA
(See EDS460/490 manual, Chap. 6.6.3.2)
Test current limiting for supply systems < 40 V
Type of sup-
ply system
EDS470
min. max.
EDS473
min. max.
DC
AC
3AC
10 mA 25 mA
25 mA 25 mA
25 mA 25 mA
1 mA 2.5 mA
2.5 mA 2.5 mA
2.5 mA 2.5 mA
Please note:
In supply systems to be monitored with a voltage < 40 V the
maximum test current of all IRDH575B1 versions is
limited to approximately 25 mA .