EasyManua.ls Logo

Benning IT 110 - Page 35

Benning IT 110
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
Connect the test cable to the BENNING IT 110/ BENNING IT 120 B.
Step 2 Set the following measuring parameters:
- Nominal differential trip-out current
- RCD type
Step 3 Followtheconnectiondiagramshowningure5.15(seethechapterContact voltage)
to perform the RCD autotest. Use the Help function if necessary.
Step 4 Check the displayed warnings and online voltage/terminal monitor before starting the
measurement. If OK, press the TEST key. The autotest sequence starts to run as follows:
1. Trip-out time measurement with the following measurement parameters:
- Test current ½×I
N
- Test current started with the positive half-wave at 0°
Measurement does not normally trip an RCD. The following menu is displayed:
Fig. 5.22: Step 1 RCD autotest results
After performing step 1 the RCD autotest sequence automatically proceeds with step 2.
2. Trip-out time measurement with the following measurement parameters:
- Test current ½×I
N
- Test current started with the negative half-wave at 180°
Measurement does not normally trip an RCD. The following menu is displayed:
Fig. 5.23: Step 2 RCD autotest results
After performing step 2 the RCD autotest sequence automatically proceeds with step 3.
3. Trip-out time measurement with the following measurement parameters:
- Test current I
N
- Test current started with the positive half-wave at 0°
Measurement normally trips an RCD within allowed time period. The following menu is displayed:
Fig. 5.24: Step 3 RCD autotest results

Table of Contents

Related product manuals