I52 & I53: FDT (Frequency Detection) Level & FDT Bandwidth
Range: 0 - 400Hz (Default: I52 - 30.00Hz, I53 - 10.00Hz)
Description: I52 sets the target frequency used in parameters in I54. Cannot be set higher
than F21.
Related Functions: I54 (Multi-function Output)
I54: Multi-function Output Define (MO)
Range: 0 - 18 (Default: 12)
Description: This parameter sets the function of the MO open collector output.
119
6 - Parameter Descriptions
Setting Range
Select Display Description
FDT-1 0 Output frequency arrival detection
FDT-2 1 Specific frequency level detection.
FDT-3 2 Frequency detection with pulse.
FDT-4 3 Frequency detection 1 with contact closure.
FDT-5 4 Frequency detection 2 with contact closure.
Overload (OL) 5 Overload detection.
Inverter Overload (IOL) 6 Inverter overload detection.
Motor stall (STALL) 7 Stall prevention mode detection.
Overvoltage Trip (OV) 8 Over voltage detection.
Low voltage trip (LV) 9 Low voltage detection.
Inverter Overheat (OH) 10 Overheat detection.
Command loss 11 Lost command detection.
During Run 12 Inverter running detection.
During Stop 13 Inverter stop detection.
During constant run 14 Steady speed detection.
During speed searching 15 Speed search mode detection.
Wait time for run signal
input
16
Fault relay output select 17
Warning for cooling fan
trip
18