Control Terminals
3.6 Control Circuit Terminals
z Note:
•
Tie the control wires no more than 15cm away from the control terminals. Otherwise, it
interferes with front cover reinstallation.
•
Use copper wires rated 600V, 75W and higher.
•
Use the recommended tightening torque when securing terminal screws.
•
When you use external power supply (24V) for multi-function input terminal (P1-P8),
terminals will be active above 12V level. Take caution not to drop the voltage below
12V.
25
3 - RECEIVING AND INSTALLATION
S-
S+
MO
MG
24
P1
P2
CM
P3
P4
CM
3B
P5
3A
P6
3C
P7
P8
VR
V1
I
AM
Terminal Name Description
P1-P8 Multi-function input terminal 1-8 Used for multi-function input.
CM Common Terminal Used for input signal common.
VR
Power Supply for external
potentiometer
Used as power for the analog frequency setting.
Maximum output is +12V, 100mA, Potentiometer
1-5kohm.
V1 Input terminal for voltage operation
Used for frequency reference and uses 0-10V for
input. Maximum input voltage: -12~+12V input.
I Input terminal for current operation
Used for frequency reference and uses 0-20mA
input. Internal resistor:500W.
AM
Multi-function analog output
terminal
Analog/digital output (For external monitoring)
Max. output voltage: 11V, Max. output current:
100mA
MO
Multi-function open collector
output
Use after defining the multi-function output
terminal.
DC24V, 50mA,or less.
MG
Ground terminal for external power
supply
24 24V external Power supply Maximum output current: 100mA
3A
Multi-function relay output A
contact
Activates when the protective function is
operating. AC250V 1A or less.
Fault: 3A-3C short (3B-3C open)
Normal: 3B-3C short (3A-3C open)
3B
Multi-function relay output B
contact
3C Common for multi-function relays
S+, S- Communication port
Communication port for MODBUS-RTU
communication.