Troubleshooting
8.6 Troubleshooting
149
8 - Troubleshooting & Maintenance
Condition Check Point
The motor
does
not rotate
1) Main circuit inspection
Is the input(line) voltage normal.(If the LED in the drive is lit)
Is the motor connected correctly?
2) Input signal inspection
Do the operating signal input to the drive.
Do the forward and the reverse signal input simultaneously to the drive?
Do the command frequency signal input to the drive.
3) Parameter setting inspection
Is the reverse prevention (FU1-03) function set?
Is the operation mode (FU1-01) set correctly?
Is the command frequency set to 0?
4) Load inspection
Is the load too large, or is the motor restrained.(mechanical brake)
5) Other
Is the alarm displayed on the keypad, or the alarm LED (STOP LED blinks)
lit.
The motor
rotates at
opposite
directions
Is the phase sequence of the output terminal U,V,W correct.
Is the starting signal (forward/reverse) connected correctly?
The
difference
between the
rotating speed
and the
reference is
too big
Is the frequency reference signal correct.(Check the level of the input
signal)
Is the following parameter setting is correct.
Lower Limit Frequency(FU1-24), Upper Limit Frequency(FU1-25), Analog
Frequency Gain(I/O-1~10)
Is the input signal line is influenced by external noise.(Use a shielded wire)
The drive
does not
accelerate or
decelerate
smoothly
Is the acceleration/deceleration time is set too short.
Is the load too large?
Is the Torque Boost (FU1-27, 28) value is too high that the current limit
function and the stall prevention function do not operate.
The motor
current is too
high
Is the load too large?
Is the Torque Boost Value (manual) too high?
The rotating
speed does
not increase
Is the Upper Limit Frequency (FU1-25) value is correct.
Is the load too large?
Is the Torque Boost (FU1-27, 28) value is too high that the stall prevention
function (FU1-59, 60) does not operate.
The rotating
speed
oscillates
when the
drive is
operating.
1) Load inspection
Is the load oscillating?
2) Input signal inspection
Is the frequency reference signal oscillating?
3) Other
Is the wiring too long when the drive is using V/F control.(over 500m)