F60: Stall Prevention Level
Range: 30-150% (Default: 150%)
Description: This parameter sets the amount of current to activate stall prevention
function during Accel, Constant or Decel run.
The set value is the percentage of the H33 [Motor rated current].
F60 is used to prevent the motor from stalling by reducing the drive output
frequency until the motor current decreases below the stall prevention level.
This function can be selected for each mode of acceleration, steady speed
and deceleration via bit combination.
During acceleration: Motor starts deceleration when current exceeding the
value set in F60 flows.
During constant run: Motor decelerates when current exceeding the value
set in F60 flows.
During deceleration: Motor deceleration is stopped when drive DC link
voltage rises above a certain voltage level.
F60: The value is set as the percent of motor rated current (H33).
z Note: The set value is the percentage of H33 [Rated Motor Current].
6.3 Function Group 2
H0: Jump Code]
Range: 0-95 (Default:1)
Description: This parameter allows the user to "jump" to any parameter without scrolling
through the group. Enter the desired parameter number, and the drive will
"jump" to that parameter.