3.9 Recommended AC Reactors
3.9.1
Keypad
Wiring the Keypad
Keypad is installed before shipping for standard type models as shown below. When using
an optional remote cable, install the buffer cover and connect the remote cable. If the
keypad is not connected properly, the letters will not be displayed.
z Note: Do not connect the keypad and remote cable while the drive power is introduced.
z Note: Do not touch the live part of the keypad connector. Doing this may cause personal
injury or electric shock.
33
3 - RECEIVING AND INSTALLATION
Keypad
(Detachable
)
Model
External Fuse
AC Reactor
Current[A] Voltage[V]
RSi001GX2B 10A 500 2.13mH, 5.7A
RSi002GX2B 15A 500 1.20mH, 10A
RSi003GX2B 25A 500 0.88mH, 14A
RSi005GX2B 40A 500 0.56mH, 20A
RSi001GX4B 10A 500 8.63mH, 1.3A
RSi002GX4B 10A 500 4.81mH, 4.8A
RSi003GX4B 20A 500 3.23mH, 7.5A
RSi005GX4B 20A 500 2.34mH, 10A
Short Circuit Rating
"Suitable For Use ON a Circuit Capable of Delivering Not More Than 5,000RMS Symmetrical
Amperes. 240V drives or 480V drives Volts Maximum."
Short Circuit FUSE/BREAKER Marking
Use Class H or K5 UL Kisted Input Fuse and UL Listed Breaker Only. See the table above for the
voltage and current rating of the fuse and the breaker.