Parameter Code List <Common area>
7.6 Parameter code list <Common area>
<Common area>: Area accessible regardless of drive models (Note 3)
133
7 - Remote Communication
Address Parameter Scale Unit R/W Data Value
0x0000 Drive model R
0: SV-iS35:SV-iV5
1: SV-iG7: SV-iG5
2: SV-iV8: SV-iC5
3: SV-iH9: SV-iP5
4: SV-iS5A: SV-iG5A
0x0001 Drive capacity R
FFFF:0.4kW 0000: 0.75kW
0002:1.5kW
0003: 2.2kW 0004: 3.7kW
0005:4.0kW
0006: 5.5kW 0007: 7.5kW
0x0002 Drive Input Voltage R
0: 220V class
1: 440V class
0x0003 S/W Version R
(Ex) 0x0100: Version 1.0
0x0101: Version 1.1
0x0004 Parameter Lock R/W
0: Lock (default)
1: Unlock
0x0005
Frequency
Reference
0.01 Hz R/W Starting freq. ~ Max. freq.
0x0006
Run Command
(Note 1)
R/W
Bit 0: Stop (S)
Bit 1: Forward run (F)
Bit 2: Reverse run (R)
W
Bit 3: Fault reset (0->1)
Bit 4: Emergency stop
- Bit 5: Not used
R
Bit 6-7: Output freq. arrival
0(Terminal), 1(keypad)
2(Reserved), 3(communication)
Bit 8-12: Freq. command
0-8: Multi-step speed freq. (0,2-8)
9-11: UpDown (Up, Down, UDZero)
12-16: Analog (V0,V1,I,V0I,V1I)
17: Jog, 18: PID, 19: Communication
20-31: Reserved
- Bit 15: Not used
0x0007 Acceleration Time 0.1 sec R/W
0x0008 Deceleration Time 0.1 sec R/W
0x0009 Output Current 0.1 A R
0x000A Output Frequency 0.01 Hz R
0x000B Output Voltage 0.1 V R
0x000C DC Link Voltage 0.1 V R
0x000D Ouput Power 0.1 kW R

Table of Contents