8.6.2 Motor Speed is not equal to the Command Frequency
151
8 - Troubleshooting & Maintenance
VFD IS LIMITING TORQUE
BASED ON USER SETTINGS.
DISABLE OR RECONFIGURE
TORQUE LIMITING, OR
ADJUST MOTOR LOAD
CONSULT
FACTORY
VFD IS SKIPPING OVER
USER-SET FREQUENCY
RANGES.
DISABLE OR RECONFIGURE
SKIP FREQUENCIES
REDUCE ACCEL/DECEL TIME
VERIFY AI CONFIGURATION
AND SIGNAL PRESENCE
VERIFY SERIAL
COMMUNICATIONS
ARE SKIP
FREQUENCIES
ENABLED?
TORQUE LIMIT
ENABLED?
ARE
ACCEL/DECEL
TIMES VERY
LONG?
IS
REFERENCE
SOURCE
SET TO
ANALOG
IN?
IS
REFERENCE
SOURCE SET
TO
SERIAL?
Y
N
Y
N
Y
N
Y
N
Y
N