H1-H5: Previous Fault History1-5
Range: (Default: nOn)
Description: This code displays the status of the five previous faults. Use the [FUNC],
[p] and [q] key before pressing the [RESET] key to check the fault
content(s), output frequency, output current, and whether the drive was
accelerating, decelerating, or at constant speed at the time the fault occurred.
Press the [FUNC] key to exit. The fault content will be stored in H1 through
H5 when the [RESET] key is pressed. H6 erases all fault histories of H1 to
H5 from the memory.
When a fault occurs during operation, it can be monitored in the nOn.
H6: Reset Fault History
Range: 0(No), 1(Yes), (Default: 0)
Description: Clears the fault history saved in H1-5.
H7: Dwell Frequency
Range: 0.1-400Hz (Default: 5.00Hz)
Description: When run command is issued, the drive will output the dwell frequency for
the amount of time in H8 before accelerating. [Dwell frequency] can be set
within the range of F21- [Max frequency]. This function is used to output a
torque into an intended direction. This is useful in a hoisting applications to
get enough torque before releasing the mechanical brake. If the dwell time is
set at '0', this function does not work.
H8: Dwell Time
Range: 0-10sec. (Default: 0.0sec.)
Description: Sets the time for dwell operation. In dwell operation, the drive outputs AC
voltage not DC voltage.
z Note: DC Injection Braking does not output a torque to an intended
direction. It is just to hold the motor.
84
6 - Parameter Descriptions