[FDT-3]
MO-MG is CLOSED when the output frequency reaches the band centered
on the FDT frequency. The output is OPENED when the output frequency
goes outside the I53 (FDT bandwidth) centered on the I52 (FDT frequency).
Detecting Condition:
Value (Freq Detection (I52)-Output Freq)<= Freq
Detection Bandwidth (I53)/2.
[FDT-4]
MO-MG is CLOSED when the output frequency reaches the I52 (FDT
frequency). The output is OPENED when the output frequency goes below
the I53 (FDT bandwidth) centered on the I52 (FDT frequency).
121
6 - Parameter Descriptions
[MO configured as ‘FDT-3’]
MO-MG
ON
Output Frequency
Reference Frequency
Tim
e
Tim
e
I53/ 2
ON
I52
[MO configured as ‘FDT-4’]
MO-MG
Output Frequency
Tim
e
Tim
e
I53
CLOSED
I52