I61: Baud Rate
Range: 0 - 4 (Default: 3)
Description: This parameter sets the baud rate for serial communications. The following
baud rates may be assigned:
Display: Baud Rate Assigned:
0 1200 bps
1 2400 bps
2 4800 bps
3 9600 bps
4 19200 bps
I62: Drive Mode Select After Loss
Range: 0 - 2 (Default: 0)
Description: It is used when frequency command is given via V1 /I terminal or RS485.
When no frequency command is given for the time set in I63, set the drive
as the table below.
Display:
Function:
0 Continuous operation at the frequency before its command
is lost.
1 Free Run stop (Coast to stop)
2 Decel to Stop
I63: Wait Time after Loss of Frequency Command
Range: 0.1 - 120 sec. (Default: 1.0 sec.)
Description: This is the time the drive determines whether there is an input frequency
command or not. If there is no frequency command input during this time,
the drive starts operation via the mode selected at I62.
I64: Communication Time Setting
Range: 2-100ms (Default: 5ms)
Description: Frame communication time.