F4: Stop Mode Select
Range: 0 - 2 (Default: 0)
Description: This parameter sets the stopping method for the drive.
Display:
Function:
0 Decelerate to stop
1 DC brake to stop
2 Free run to stop
Decel:
The drive stops using the deceleration pattern. Select 0 in F30.
DC-brake:
The drive stops with DC injection braking. The drive will output
a DC voltage when the frequency goes below the DC injection braking
frequency during deceleration (see F8-F11, page 68-69).
Free-run (Coast to stop):
The drive stops outputting voltage immediately
when the stop signal is commanded.
67
6 - Parameter Descriptions
Output Frequency
Time
FX -CM
ON
Output Voltage
Time
Time
Stop Command
[Stop Mode: 'Decel']
Output Frequency
Time
FX -CM
ON
Output Voltage
Time
Time
Stop Command
[DCBr Freq]
[DCBr Value]
t1 t2
t1: FUN -24
t2: FU N-26
[Stop Mode: 'DC-brake']
Output Frequency
Time
FX -CM
ON
Output Voltage
Time
Time
Stop Command
Output cutoff
Output cutoff
[Stop Mode: 'Free-run']