F39: Output Voltage Adjustment
Range: 40-110% (Default: 100%)
Description: This function is used to adjust the output voltage of the drive. The set value
is a percentage of input voltage. This is useful when using a motor that has
lower rated voltage than the main input voltage. When this is set at 100%,
drive outputs its rated voltage.
z Note: the drive output voltage does not exceed the main input voltage,
even though F39 is set at 110%.
77
6 - Parameter Descriptions
Output Voltage
100%
50%
Output Frequency
Base Freq.
When set to 50%