39Local Controls
Section 6: Local Controls
1. Alphanumeric display: during normal operation the alphanumeric display shows
the present status (NORMAL, ESD ON, ALARM, WARNING, INTERLOCK), the
3-position selector status (LOCAL, OFF, REMOTE) and the actuator action (OPEN,
OPENING, CLOSED, CLOSING, STOP or R% : xxx.x). If the local selector is in OFF or
REMOTE, pressing the YES pushbutton, it is possible to scroll the list of variables,
alarms and reports:
— output torque mot temp
— motor speed term temp
— main voltage log status
— current wireless report
— temperature node report *
— time FDI report *
— date base report
— alarm term report
— warning Ain/Aout report *
— Ktemp
The data with * are only present if the relevant modules are present.
2. 3-position selector to set the following operation modes:
— LOCAL: for local control only
— OFF: no control is active but the actuator is still connected to the mains
— REMOTE: for remote control only
3. The F01-2000 can be provided with a radiofrequency wireless connection based
on a qualied Bluetooth™ class 1 module. This allows to establish a connection
and exchange data with a PDA or PC with built-in Bluetooth™ technology. The
following tasks can be wirelessly performed:
— View and change conguration
— Set maintenance function
— Read maintenance data
— Download new rmware to the F01-2000
— The blue LED indicates that the communication with a host device
is established
4. Numeric display to indicate the present valve position as a % of the opening.
Display resolution in function of the actuator stroke turns:
— From 2.8 to 5.5 turns = 1%
— From 5.5 to 13.8 turns = 0.5%
— From 13.8 to 27.7 turns = 0.2%
— From 27.7 to 10,000 turns = 0.1%