24.5 MKT (E4) technical data
Chamber size
115
240
720
Exterior dimensions
Width, gross (including 18 mm for 1 ac-
cess port (MKT 115, 240), 36 mm for 2
access ports (MKT 720), with plug)
mm / inch 1000/ 39.37 1135/ 44.69 1615/ 63.58
Height, gross (incl. castors)
mm / inch
1725/ 67.91
1940 / 76.38
2005 / 78.94
Depth, gross (incl. cable and door handle)
mm / inch
915/ 36.02
1000/ 39.37
1230/ 48.43
Depth, gross (incl. cable and door handle)
with optional compressed air dryer
mm / inch 1085 / 42.72 1170 / 46.06 1400 / 55.12
Depth, gross (incl. cable and door handle)
with voltage and frequency changer
mm / inch 1530 / 60.24 1615 / 36.58 1845 / 72.64
Wall clearance rear (minimum)
mm / inch
300 / 11.81
300 / 11.81
300 / 11.81
Wall clearance rear with optional com-
pressed air dryer or to set up the voltage
and frequency changer (minimum)
mm / inch
1000 / 39.37 1000 / 39.37 1000 / 39.37
Wall clearance sides (minimum)
mm / inch
200 / 7.87
200 / 7.87
200 / 7.87
Window width
mm / inch
288 / 11.34
508 / 19.99
508 / 19.99
Window height
mm / inch
222 / 8.74
300 / 11.81
300 / 11.81
Doors
Number of doors
1
1
1
Interior dimensions
Width
mm / inch
600 / 23.62
735 / 28.94
1200 / 47.24
Height
mm / inch
480 / 18.90
700 / 27.56
1020 / 40.16
Depth
mm / inch
400 / 15.75
443 / 17.44
600 / 23.62
Interior volume
l / cu.ft.
115 / 4.06
228 / 8.05
734 / 25.92
Racks
Quantity of racks (regular)
1
1
1
Quantity of racks (max.)
4
6
11
Maximum load per rack
Kg / lbs.
30 / 66
30 / 66
40 / 88
Maximum permitted total load
Kg / lbs.
60 / 132
70 / 155
160 / 353
Weight
Weight (empty)
Kg / lbs.
305 / 672
380 / 838
610 / 1345
Weight (empty)
with optional compressed air dryer
kg / lbs. 320 / 705 395 / 871 625 / 1378
Temperature data
Temperature range
°C
°F
-70 to +180
-94 to 356
-70 to +180
-94 to 356
-70 to +180
-94 to 356
Temperature fluctuation
± K
0.1 to 0.6
0.1 to 0.4
0.1 to 0.5
Temperature uniformity (variation)
± K
0.2 to 1.8
0.1 to 1.0
0.3 to 2.0
Average heating up time
acc. to IEC 60068-3-5
K/min. 5.3 5,0 4,5
Average cooling down time
acc. to IEC 60068-3-5
K/min. 4.2 4.2 4.2
Max. heat compensation at 25 °C / 77°F
W
1800
3000
5500