EP600 Energy Storage System User Manual
up it. If the symptom persists, please contact
BLUETTI support team.
Check if the total voltage of solar panels exceeds
the limit. Reduce the number of solar panels and
the inverter resumes operation after calibration.
Check the insulation resistor between solar array and
grounding for a short circuit.
GFCI Hardware Circuit
Failure
Turn off the inverter and wait 30 minutes to restart
up it. If the symptom persists, please contact
BLUETTI support team.
Check if the AC output PE wire is grounded.
Check if the grid connection meets installation
requirements.
Check if the inverter fan operates well.
Turn off the inverter and wait 30 minutes to restart
up it. If the symptom persists, please contact
BLUETTI support team.
Hardware Input Overcurrent
Check if the DC voltage is too low.
Check if the DC voltage is inconsistent with the battery
specifications.
Turn off the inverter and wait 30 minutes to restart
up it. If the symptom persists, please contact
BLUETTI support team.
Check if the inverter is overloaded.