User’s Manual
37
6. Click “Scan to confirm that the changes you made were
accepted.
Multiple modules can be configured from the same PC at the same
time.
4.2.6.1.3. ONLINE MODULE CONFIGURATION THROUGH A WEB BROWSER
The IP address can be changed using a standard web browser.
Perform the following steps.
1. Power on the braking kit.
2. If you don’t know the IP address of the module, you can use the
hardware switches to temporarily force it to a standard address
and make the stored IP address change as below.
3. Use a standard web browser to connect to the braking module.
The web page configuration is compatible with Internet Explorer
and Firefox. Others should work as well. To connect, put the
IP address directly in the address bar of the browser.
4. This webpage can be used to drive the inputs and observe the
outputs of the braking module. Use care, as bits set here will
affect the actual operation of the chopper.
5. Configure the module with the desired IP address, subnet mask,
gateway, DNS servers, and DHCP configuration. There is not
SMTP configuration available, this can be left blank.
6. Press “Store Configuration to change the settings. This
change is not immediate; power must be cycled before the
change takes place. If you had hard set the IP address with the
configuration switches, make sure you turn all the switches off.
4.2.6.1.4. PLC CONFIGURATION
The EDS file for the network module may be found by visiting the
Bonitron website. Load the EDS file onto your PLC according to
your PLC manufacturer’s instructions. Configure both the input and
output data ranges to a size of 128 bytes, and the RPI time to 100
mS.
If instructed by the PLC for the Assembly Instance, such as the
RSLogix 5000, use any non-zero value.
4.2.6.1.5. ETHERNET / IP STATUS INDICATORS
These LEDs indicate run time status and errors to the user. During
power up, a LED test sequence is performed according to the
EtherNet / IP specification.