108 en | Approved applications Control Panels
2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Rothenbuhler 5110/4001-42 High Security Bell to control panel wiring
USB POWER
STATUS
L
I
N
K
ETHERNETUSB
B
A
S
E
T
11
13 14
16
17
19
20
22
12
15
18
21
Quick Flash:
Low
BATTERY STATUS
Slow Flash:
Charging
Off: Normal
On:
Missing
Low 12.1 VDC
Load Shed 10.2 VDC
EARTH GROUND
COMMON
BATTERY (
-
)
+ AUX POWER
BATTERY ( + )
CLASS 2
16.5 VAC 40 VA 60 Hz
TRANSFORMER
10
9
8
7
6
5
4
3
2
1
OUTPUT
B (2)
OUTPUT
A (1)
OUTPUT
C (3)
Do not connect
to a receptacle
controlled by
a switch.
Point 5 Point 6
Point 3 Point 4
Point 1 Point 2 Point 7 Point 8
ON-BOARD POINTS
1 k End-of-line-Resistors Required (P/N 15093130-004),
WARNING!
Multi-Battery
installation requires
Model D122 or D122L
Dual Battery Harness.
Improper installation
can be a fire hazard
.
WARNING!
Incorrect wiring will
damage this
equipment.
Devices powered by
any output must be
supervised.
POWER SUPPL
The Power S
refer to the B
The system is intended
panel has been approv
RevPol.
Battery: Replace every 3 to
5 years with one or two
Model D126 or D1218 12V
Lead Acid Batteries.
WARNING!
To prevent risk of shock,
disconnect AC power and
communication lines before
servicing.
All exte
Require
Voltage Ranges: Open 3.7 - 5.0 VDC,
Owner I
be removed by
POINT 1 COM POINT 2 POINT 3 COM POINT 4 POINT 5 COM POINT 6 POINT 7 COM POINT 8
Callout á…³ Description Callout á…³ Description
1 á…³ 5110 Logic Board 8 á…³ Alarm input point*
2 á…³ 4001-42 External Line Balancing Module 9 á…³ Common
3 á…³ +AUV POWER 10 á…³ Optional silence switch
4 ᅳ 10 kΩ resistor 11 ᅳ D133 Relay Module
5 á…³ Control panel 12 á…³ BBL In 4
6 á…³ Alarm output 13 á…³ BBL Out 5
7 á…³ Alternate alarm 14 á…³ Terminal TB1
*
Use Terminal 11, 13, 14, 17, 19, 20, or 22. (Select only one.)
Notice!
Bell Test at Arming
UL Standard 365 requires a Bell Test at arming for bank safe and vault applications.
System configuration requirements
The following configuration and programming options are required for UL Bank Safe and Vault
Systems. Refer to RPS Help, the Installer Services Portal programming tool (available in
Europe, Middle East, Africa, and China) Help, or the control panel’s Program Entry Guide for
programming information.